Setting Cooling curve setting 1
Index - String
MIN
value
MAX
value
Parameter function
-20°C 26°C
This parameter indicates the maximum value of the cooling set temperature, correspon-
ding with the minimum outside air temperature (index (7) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
Setting Cooling curve setting 2
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the minimum outside air temperature taken into consideration
for cooling compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting Cooling curve setting 3
Index - String
MIN
value
MAX
value
Parameter function
-20°C 26°C
This parameter indicates the minimum value of the cooling set temperature, correspon-
ding with the maximum outside air temperature (index (9) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
Setting Cooling curve setting 4
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the maximum outside air temperature taken into consideration
for cooling compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting heating curve set 1
Index - String
MIN
value
MAX
value
Parameter function
25°C 65°C
This parameter indicates the maximum value of the heating set temperature, correspon-
ding with the minimum outside air temperature (index (b) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
Setting heating curve set 2
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the minimum outside air temperature taken into consideration
for heating compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).