Air temperature limit 2
Index - String
MIN
value
MAX
value
Parameter function
-25°C 45°C
This parameter indicates the outside air temperature corresponding to the maximum
water temperature limit (St2 parameter, r indicator) that can be produced by the com-
pressor.
Water temperature limit 2
Index - String
MIN
value
MAX
value
Parameter function
0°C 70°C
This parameter indicates the maximum water temperature limit produced by the com-
pressor with outside air temperature equal to parameter LA2 (indicator q).
Maximum heating set point limit
Index - String
MIN
value
MAX
value
Parameter function
0°C 70°C
This parameter indicates the maximum temperature level that the user can set as a hea-
ting Setpoint value (parameter StC, indicator 3, user menu).